Part Number Hot Search : 
M62354FP 2SAR542P MA4100 4GIFD GRM21 B104J TDA9814T C24FJ64G
Product Description
Full Text Search
 

To Download APT-DINAV53G3 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 Energy Management 3-channel Power Transducer Type APT-DIN
* Measurement of: kW * 9 selectable full-scales in 9 intervals from 0 to 5 (range from 0,4kW to 3,6kW) * Degree of protection (front): IP 50 * 3 analogue outputs (0 to 10VDC) * Response time: 50ms
Product Description
Active power transducer with auxiliary power supply of 400VAC (phasephase connection). 9 measuring ranges selectable in 9 intervals from 0 to 5 (measuring range from 0,4 to 3,6kW) The house is for DIN-rail mounting and ensures a degree of protection (front) of IP 50.
Ordering Key
Model Range code System Power supply Rated outputs Number of inputs Calibration
APT-DINAV53G3 2 1
Type Selection
Range code AV5: 400 VAC - 5,2 AAC (max. 480 V (L-L) 6,2 A) (standard) System 3: Three phase system (3 wires, balanced/ unbalanced load) Power supply D: G: Number of inputs 2: 2 x (3-phase inputs) Calibration 1: 3600W. 230VAC -15+10% 50/60Hz 400VAC -15+10% 50/60Hz Rated outputs 3: 3 x (0 to 10VDC)
Input Specifications
Rated inputs Accuracy Active power (@ 25C 5C, R.H. 60%) Additional errors Humidity Input frequency Magnetic field Ripple 2 (3-phase inputs) for current and voltage measurements 3% rdg (cos 0.7 L/C, 0.5 to 1Ph) < 0.5%, 60% to 90% R.H. < 0.5%, 50 to 60 Hz < 0.5% @ 400 A/m balanced load: 1% according to IEC 60688-1 and Measurement Ranges (impedances) AV5: Frequency range Over-load protection Continuous: voltage/current For 1 s Voltage: Current: EN 60 688-1 unbalanced load: 5% kW 400VAC (2W per channel) 5.2AAC (0.3 VA per channel) 48 to 62 Hz 1.2 x rated input 2 x rated input 20 x rated input
Output Specifications
Analogue outputs Number of outputs Range Response time Temperature drift Load: 10 V output 3 (one per channel) 0 to 10 VDC 50 ms typical 500 ppm/C 10 k Analogue outputs Insulation By means of optocouplers, 2000 Vrms output to measuring input / power supply
Specifications are subject to change without notice
APT-DIN 3 DS0603
1
APT-DIN
Supply Specifications
AC voltage 400 VAC (standard), -15%+10% 50/60 Hz 230VAC (optional) -15+10% 50/60Hz Power consumption 7 VA
General Specifications
Operating temperature Storage temperature Insulation reference voltage -20 to +60C (-4 to 140F) (R.H. < 90% non-condensing) -30 to +80C (-22 to 176F) (R.H. < 90% non-condensing) 300 Vrms to ground (with neutral connection), CAT II (double insulation), CAT III (main insulation) Pollution degree 2 4000 Vrms between all inputs/ outputs to ground 4000 Vrms for 1 minute Noise rejection CMRR EMC Safety standards Safety requirements: Products requirements: Connector Housing Dimensions Material Degree of protection Weight 100 dB, 48 to 62 Hz EN 50081-1, EN 50082-1 IEC 61010-1, EN 61010-1 IEC 60688-1, EN 60688-1 Screw-type, max. 4 mm2 wires 115 x 76 x 100 mm ABS, self-extinguishing: UL94 V-0 Front: IP50 Approx. 810 g (packing included)
Insulation Dielectric strength
Wiring Diagrams
Three-phase, 3-wire ARON input connections - Unbalanced loads
Front Panel Description
4
1
2 3
CT connection (3-wire system)
1. Rotary switch 9-position rotary switch for input full scale selection (at every selected input full scale correspond a 10VDC output) . 2. LED Power-ON. 3. Connection terminal blocks 4. Connection terminal blocks
Dimensions
2
APT-DIN 3 DS0603
Specifications are subject to change without notice


▲Up To Search▲   

 
Price & Availability of APT-DINAV53G3

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X